IQ Pro range including “SIL” Safety Function Control Module option is TÜV certified for use in SIL 2 safety applications using a 1 out of 1 actuated valve configuration (1oo1). Safety functions are “Stayput” and “ESD”. The SIL option can be included with any new IQ or IQT range actuator or be retrofitted to existing actuators supplied since 2000.
Where SIL 3 is required, IQ Pro-SIL may be used in a 1oo2 actuated valve configuration.
TÜV Approval Certificate: Z10 07 09 64590 001
For 50 years Rotork have held reliability as the dominant factor in both the design and manufacturing of electric actuators and accordingly have gained industry recognition for reliable actuation.
With the advent of standards for
determining process functional safety requirements, the reliability of equipment within Safety Instrumented System (SIS) to carry out the required safety function and meet the target Safety Integrity Level (SIL) must be defined by design with auditable reliability data.
Rotork have brought inherent design rigor of the IQ Pro range together with the design requirements of Standards IEC61508 and IEC 61511 to provide the first “SIL” certified electric valve actuator independently certified by TÜV.
Established Leaders in Valve Actuation Technology
Publication E1121EIssue 10/07
IQ Pro SIL option
Operation
TÜV Certified for use in SIL 2 & 3 applications
Safety Functions
The two safety functions applicable to valve actuators are:Safety function 1 - Stayput (High Demand)
The actuator shall not move without a valid remote open or close command signal. If an internal failure is detected the actuator will give an alarm signal.
Dual hardwired control input signals are required for remote control. Signals must be maintained, “push to run“ type only. Safety function 1 is available with IQ and IQT Pro ranges.Safety function 2 - ESD (Low Demand)
If an ESD signal is active the actuator will perform the commissioned ESD action (open, close or stayput). If an internal failure is detected the actuator will give an alarm signal.
ESD signal must be derived from a contact breaking and must be maintained during ESD. Safety function 2 is available with IQ Pro range only.
Combined Safety Functions 1 & 2 – Stayput with ESDTo stayput as per safety function 1, else perform the commissioned ESD action as per safety function 2. ESD has priority. Combined Safety function 1 & 2 is available with IQ Pro range only.
The SIL option monitors the standard IQ Pro control board and provides diagnostic coverage and redundant control in order to carry out its safety function if required. In addition, electro-mechanical and mechanical component reliability has been assessed & quantified, meeting reliability requirements of SIL2/3 applications.
A safety function status relay provides indication of the
actuator availability, redundant safety function operation and control signal status. Status is also duplicated locally on the actuator display.
In order to meet the requirements of SIL2/SIL3 as
certified by TÜV, IQ Pro-SIL actuators must be installed, commissioned, operated and maintained/ proof tested in accordance with the safety manual publication E173E3.
Available IQ Pro – SIL Actuator types
For the types shown below there is no restriction on actuator size or speed. Refer to Publication E110E for actuator sizes, speeds and torque performance details.
Due to the strict design and implementation requirements necessary, IQ Pro – SIL option is limited to the actuator types and options ONLY displayed in the table below:
* requires addition of second stage gearbox
** Where a 4-20mA position feedback signal is required, option Current Position Transmitter (CPT) is available. CPT Output signal is not part of the safety function. CPT is 24V DC (nominal) loop powered and will output 4mA on loss of actuator power supply irrespective of position.
Established Leaders in Valve Actuation Technology
IQ - SIL Reliability data for SIL 2 applications
The reliability data provided is applicable to the complete actuator up to and including the actuator output drive assembly. It does not include the valve, valve drive
components or second stage gearboxes. The integrity/reliability of the electrical power supply and user derived control signals are not included in the actuator reliability assessment.
* Approval for SIL 2 applications based on the stated periods. Users must ensure these intervals are not exceeded in service.
IQ Pro SIL option
Actuator selection and sizing
TÜV Certified for use in SIL 2 & 3 applications
Actuator Indication
Fault Status Relay
The SIL option includes a status relay contact providing remote indication that the system has detected an invalid or fault condition and has performed the safety function, or, the
safety function cannot be applied or could be overridden. The actuator LCD display also provides fault status indication.Indication Contacts
The actuator has 4 configurable contacts, S1 to S4 available for indication including open and closed position limit
indication and intermediate position indication (configurable).
A full list of available functions is provided in publication E170E3.
The selection of actuator type and size is dependent on the valve type (multi-turn or part-turn) and the required operating forces (torque and/or thrust). Actuator performance data is provided in publication E110E. An on-line actuator sizing guide is available at . Contact Rotork for further help or advice.
The following conditions will be applied:
Rotork will size the actuator based on the supplied valve
data. No additional safety factors will be added unless expressly requested.
The valve or valve drive components must be capable of
safely withstanding the supplied actuator stall torque and/or developed thrust at stall torque. For design purposes, stall torque must be considered to be at least 3 times supplied actuator/actuator-gearbox combination rated torque.
If the SIL option takes over the control in order to carry out
Monitor Relay
The monitor relay will indicate one or more of the following conditions:
Loss of one or more of the power supply phases Loss of control circuitry supply Actuator selected for local control Thermostat tripped
Local / Remote control pushbutton set to Local stop.
an ESD to a predetermined end of travel (safety function 2), the actuator may stall against the valve or gearbox stops for a time up to the stroke time +3 seconds.
Actuator Power
The actuator electrical power supply integrity does not fall within the scope of the actuator reliability data. Users must ensure the integrity of the actuator power supply meets the requirements of the target SIL for the SIS.
The monitor relay is not configurable. Refer to actuator circuit diagram for connections.
Analogue 4-20mA position indication
Where the CPT option is fitted - refer to actuator circuit diagram, a 4-20mA loop powered signal is available for
analogue position indication. The CPT must be powered from an external source with a nominal supply of 24V DC. On loss of main actuator power supply, the CPT output will default to 4mA regardless of actuator position.
Actuator Control
Refer to control connection drawing RWS320 below and Example IQ Circuit Diagram 3000S000.
In order to meet the requirements of SIL 2 for safety function 1 the actuator must be controlled for opening and closing using 2 input signals.
Application of only one signal is invalid and will raise an error status feed back on the display and status relay.
For safety function 2, a single, maintained ESD signal derived from a normally closed contact (break to ESD) is required. ESD operation will override any existing open or close (local or remote) signal while applied.
Indication outputs S1 to S4, Monitor Relay and the CPT analogue position signal do not fall within the scope of the actuator reliability assessment and therefore should not form part of the SIS.
User must ensure the integrity of indication meets the requirements of the SIL target for the SIS. If necessary, limit position indication should be derived from devices external to the actuator and driven directly from the valve obdurator.
Established Leaders in Valve Actuation Technology
Typical Remote Control circuit diagram
IQ Pro SIL option
IQ/IQT Remote Control Circuitry forSIL2 applications - 24V DC
TÜV Certified for use in SIL 2 & 3 applications
manual publication E173E3. Unless specified with order, the actuator is despatched with default settings as listed in publication E173E3.
The infra red setting tool enables the configurable actuator
settings to be made.
To meet the requirements of TÜV certificate for SIL2/3
applications the following 24V DC remote control connections must be made. The safety integrity assessment for the remote control circuits is the responsibility of others and does not form part of the actuator assessment.
Before putting the actuator into service, it must be installed and commissioned in accordance with IQ Pro SIL safety
Note:
Actuator remote control signals may be internally or externally supplied at 24V DC (nominal). A valid open or close remote control command consists of a control input signal and
conditional input signals being applied simultaneously for the required direction of operation. Invalid signals will not cause operation and will invoke an “ERR” alarm on the display and status relay (make contact). For full status alarm conditions refer to E173E3.
Conditional control input signals are not required for local control. ESD can be user configured for Stayput, Close or Open. ESD signal must be derived from a Stayput, normally closed contact breaking.
Internally supplied:
Fit link “#” as shown and connect remote control contacts to internal supply on terminal 5.
Externally supplied:
Connect control contacts to external supply 24V DC +VE. Connect supply 24V DC -VE to terminal 36 & 31.
Note
IQT Range actuators - Wiring Diagrams 6000S000/6060S000 and 7000S000/7060S000 are not certified for use in SIL2/3 applications requiring safety function 2:ESD.
Established Leaders in Valve Actuation Technology
TÜV Certificate
IQ Pro SIL option
TÜV Certified for use in SIL 2 & 3 applications
UK head office
Rotork Controls Limited
telephone Bath 01225 733200telefax 01225 333467email mail@rotork.co.ukUSA head officeRotork Controls Inc
telephone Rochester (585) 247 2304telefax (585) 247 2308email info@
As part of a process of on-going product development, Rotork reserves the rightto amend and change specificationswithout prior notice.
Published data may be subject to change.For the very latest version release, visitour website at
Rotork Controls Ltd, Bath, UK
Rotork Controls Inc, Rochester, USA
A full listing of our worldwide sales and service network is available on our website at
The name Rotork is a registered trademark. Rotork recognizes all registered trademarks. Published and produced in the UK byRotork Controls Limited.
POWTG1007
正在阅读:
永磁调速器电动执行器说明书(1)05-11
广东省2015年高级主治医师(全科)基础知识考试题03-26
数电实验二 门电路特性参数测试 - 图文09-27
轨道工程课程设计04-23
企业文化范文02-11
第二单元我们周围的空气教案06-16
捣蛋鬼作文600字06-30
2013年政法干警招录培养考试《民法学》试卷(部分)10-25
鳕鱼肝油软胶囊 - 天才第一步 - 图文06-25
- 教学能力大赛决赛获奖-教学实施报告-(完整图文版)
- 互联网+数据中心行业分析报告
- 2017上海杨浦区高三一模数学试题及答案
- 招商部差旅接待管理制度(4-25)
- 学生游玩安全注意事项
- 学生信息管理系统(文档模板供参考)
- 叉车门架有限元分析及系统设计
- 2014帮助残疾人志愿者服务情况记录
- 叶绿体中色素的提取和分离实验
- 中国食物成分表2020年最新权威完整改进版
- 推动国土资源领域生态文明建设
- 给水管道冲洗和消毒记录
- 计算机软件专业自我评价
- 高中数学必修1-5知识点归纳
- 2018-2022年中国第五代移动通信技术(5G)产业深度分析及发展前景研究报告发展趋势(目录)
- 生产车间巡查制度
- 2018版中国光热发电行业深度研究报告目录
- (通用)2019年中考数学总复习 第一章 第四节 数的开方与二次根式课件
- 2017_2018学年高中语文第二单元第4课说数课件粤教版
- 上市新药Lumateperone(卢美哌隆)合成检索总结报告
- 调速器
- 执行器
- 永磁
- 说明书
- 电动
- 地铁前期交通疏解方案
- 新编基础会计学试卷(A卷)参考答案
- 浅谈商业银行客户经理制
- 德国代根多夫应用科技大学校企合作模式的思考
- 2010年4月外刊经贸知识选读试题真题答案
- 2016~2017学年第二学期九年级开学考试试卷 (2)
- SOFA评分在呼吸机相关性肺炎中的应用
- PLD高温光纤传感器工艺研究
- 2021年术中失血量和输血指征的正确评估及其临床意义
- 型钢混凝土异形柱抗震性能试验研究_陈宗平
- 入网工作负责人(变电部分)《安规》《两票实施细则》考试答案
- 劳务派遣管理制度(范本)
- 服装鞋业销售连锁管理系统
- 成本会计学 第2章 工业企业成本核算的要求和一般程序
- 2013届高考数学二轮复习专题专题六 立体几何 第二讲空间中的平行与垂直
- 初中化学远程学习总结
- 选举居民小组长和居民代表的居民小组会议议程学习
- 高考英语书面表达专项训练:阅读表达+写作(8)
- 矿山破碎机故障诊断与维护
- GWZ-10X柱上智能开关控制器使用手册