ACS800
ABB Drives
Hardware Manual
Drive Control UnitRDCU-02(C)
ACS800
ACS800
3
RDCU-02(C) Control Unit Hardware ManualRDCU-02(C) layout
Designations A…C and J1 refer to the section Mechanical installation below. The connectors (X…) are explained under Technical data further below.
RDCU-02(C) Control Unit Hardware Manual
ACS800
4
Safety instructions
Do not attempt any work on a powered drive. After switching off the mains, always allow the intermediate circuit capacitors 5 minutes to discharge before working on the frequency converter, the motor or the motor cable. It is good practice to check (with a voltage indicating instrument) that the drive is in fact discharged before beginning work.
Avoid touching the circuit board (RMIO) inside the RDCU-02(C) unit in order to minimise the risk of damage caused by static electricity.
Do not use excessive force when detaching connectors or removing the cover of the unit.
Identifying different types of unit
Before installation, check that the RDCU-02(C) unit has the correct application program for the converter hardware in question. There is a label attached to the cover of the RDCU-02(C) unit that lists “SW TYPE”, “SW CODE” and “DEVICE TYPE”.
“SW TYPE” identifies the application program that is loaded into the RDCU-02(C) unit. Some of the most common “SW TYPE” codes are AMXRxxxx (ACS600/800 System Application Program), ASxRxxxx (ACS600/800 Standard Application
Program), AHxRxxxx (ACS800 Pump Control Application Program), and IxxRxxxx ISU (IGBT Supply Unit Application Program). Check that the application program corresponds to the original order.
Check also that the “DEVICE TYPE” indicated matches that of the converter hardware.
Mechanical installation
General
The RDCU-02(C) can be mounted on a vertical or horizontal 35 × 7.5 mm DIN rail.The unit should be mounted so that air can freely pass through the ventilation holes in the housing. Mounting directly above heat-generating equipment should be avoided.
WARNING! Avoid installing the RDCU in the immediate vicinity of sources of
electromagnetic disturbance, such as relays, contactors, brake choppers and motor cabling. The minimum recommended distance from such components is 500 mm. Installing metallic screening between the unit and the source of disturbance is highly recommended, and may reduce the required distance.
The RDCU is grounded to the mounting rail by two screws.
RDCU-02(C) Control Unit Hardware Manual
ACS800
5
Fastening the unit to the mounting rail
Note: Set jumper J1 (if necessary; see the Isolation and grounding diagram) before fastening the unit.
Setting J1 can be further facilitated by removing the cover (see Removal and replacement of cover below for further instructions). The jumper can also be set using long-nosed pliers or tweezers without removing the cover.
Align the four retaining clips (A) at the top and bottom edges of the cover with the mounting rail, and carefully press the module onto the rail until the clips catch on the edges of the rail.
Using two screws, fasten the base plate of the RDCU by the two mounting holes
(B) to the mounting rail. Make sure the contact surfaces are free from dirt or grease. This is essential for the operation of the control unit since the screws provide the grounding for the unit.
Removal of unit from mounting rail
Remove the two screws (B) holding the base plate of the unit to the mounting rail. Carefully bend the retaining clips (A) at the upper and lower edges of the cover outwards to release the unit completely from the mounting rail.
Removal and replacement of cover
Remove all detachable (screw-type) terminal plugs from the RDCU, and disconnect any cables connected to the unit. Remove any optional modules.If desired, the unit can be removed from the mounting rail as described above to facilitate the following steps.
With a screwdriver or similar tool, carefully release the four cover retaining clips
(C) on the right-hand side while simultaneously pulling the right-hand edge of the cover gently away from the base plate.
Shift the cover to the left to free its left-hand edge, then pull it to detach it completely from the base and circuit board.
Replace the cover in reverse order to the above (left-hand edge first). If the unit is already mounted onto its mounting rail, align the retaining clips (A) so that they catch on the mounting rail.
RDCU-02(C) Control Unit Hardware Manual
ACS800
6
Wiring
General
The shields of the I/O cables should be grounded to the chassis of the cubicle as close to the RDCU as possible.
Use grommets at all cable entries.
Handle fibre optic cables with care. When unplugging fibre optic cables, always grab the connector, not the cable itself. Do not touch the ends of the fibres with bare hands as the fibre is extremely sensitive to dirt.
The maximum long-term tensile load for the fibre optic cables included is 1 N; the minimum short-term bend radius is 25 mm (1”).
Digital/Analogue input/output connections
See the Firmware Manual of the application program in question.
Installation of optional modules
Follow the instructions given in the user manual of the module.
Other connections
See also the wiring diagram below.
Powering the RDCU
The RDCU is powered through connector X34. The unit can be powered from the power supply board of the inverter (or IGBT supply) module, provided that the maximum current of 1 A is not exceeded.
The RDCU can also be powered from an external 24 V DC supply. Note also that the current consumption of the RDCU is dependent on the optional modules attached. (For current consumption of optional modules, see their respective user manuals.)Fibre optic connection to inverter/IGBT supply module
Connect the PPCS link of the AINT (ACS 800 series modules) or NINT (ACS 600 series modules) board of the inverter (or IGBT supply) module to fibre optic connectors V57 and V68 of the RDCU.
Note: The recommended maximum distances for the fibre optic link is 10 m (for plastic [POF] cable). In case longer distances are required, contact an ABB representative.
RDCU-02(C) Control Unit Hardware Manual
ACS800
7
Connection of control panel (CDP 312R)
Connect the control panel to X39.RDCU Control Unit
RMIO
X39
V68V57
RXDTXDRDCU Control UnitRMIOX39V68V57RXDTXDX34+–X34+–
I0I0
CDP 312R control panel
V41V42
NINT12R2i/R3i: NINT/X34R4i/R5i: NPOW/X34R6i/R12i: NPOW/X351 A max.V1V212R7i/R8i: APOW/X31 A max.AINT
(ACS 600 Series)
IGBT Supply or Inverter Module(ACS 800 Series)IGBT Supply or Inverter Module
RDCU-02(C) Control Unit Hardware Manual
ACS800
8
Technical data
General
Mounting: Onto 35 × 7.5 mm DIN mounting rail
Housing materials: Zinc-plated steel (base); ABS/PC (cover)
Connector types
X20 (Constant voltage output): 2-pole detachable screw terminal block*
X21 (Analogue I/O): Four 3-pole detachable screw-type terminal blocks*
X22 (Digital inputs): One 3-pole and two 4-pole detachable screw-type terminal blocks*
X23 (24 VDC output): 2-pole detachable screw-type terminal block*
X25-X27 (Relay outputs): Three 3-pole detachable screw-type terminal blocks*X31 (Slot 1), X32 (Slot 2): 38-pin header (female), pitch 2 mm
X33 (DDCS): 20-pin header (female), pitch 2.54 mm
X34 (24 VDC power input): 3-pole detachable screw-type terminal block*X39 (Control panel): 12-pin header (male), pitch 2.54 mm
V57, V68 (PPCS link): Fibre optic transmitter/receiver (10 MBd)
*Wire: 0.3 … 3.3 mm2 (22…12 AWG). Torque: 0.2 … 0.4 Nm (2…4 lbf.in.). Pitch: 5.0 mm.
Constant voltage output (X20, X21:1)
Voltage: +10 VDC, 0, -10 VDC ±0.5% (Full scale range) at 25 °C (77 °F).
Temperature coefficient: ±100 ppm/°C (±56 ppm/°F) max.
Maximum load: 10 mA
Applicable potentiometer: 1 to 10 kohm
Analogue inputs (X21)
General: Two programmable differential current inputs (0 mA / 4 mA … 20 mA, Rin = 100 ohm) and one programmable differential voltage input (-10 V / 0 V / 2 V … +10 V, Rin = 200 kohm). The analogue inputs are galvanically isolated as a group (see Isolation and grounding below)
Isolation test voltage: 500 VAC, 1 min
Max. common mode voltage between the channels: ±15 VDC
Common mode rejection ratio:Resolution: 0.025% (12 bit) for the -10 V … +10 V input, 0.5% (11 bit) for the 0 … +10 V and 0…20 mA inputs
Inaccuracy: ±0.5% (Full scale range) at 25 °C. Temperature coefficient: ±100 ppm/°C max.
RDCU-02(C) Control Unit Hardware Manual
ACS800
9
Analogue outputs (X21)
General: Two programmable current outputs: 0 (4) … 20 mA, RLResolution: 0.1% (10 bit)
Inaccuracy: ±1% (Full scale range) at 25 °C (77 °F). Temperature coefficient: ±200 ppm/°C (±111 ppm/°F) max.
Digital inputs (X22)
General: Six programmable digital inputs (common ground: 24 VDC,
-15% … +20%) and a start interlock input (DIIL). Group isolated, can be divided into two isolated groups (see Isolation and grounding below).Thermistor input: 5 mA, < 1.5 kohm “1” (normal temperature), > 4 kohm “0” (high temperature), open circuit “0” (high temperature).
Internal supply for digital inputs (+24 VDC) is short-circuit proof. An external 24 VDC supply can be used instead of the internal supply.
Isolation test voltage: 500 VAC, 1 min
Logical thresholds: < 8 VDC “0”, > 12 VDC “1”
Input current: DI1 to DI5: 10 mA; DI6: 5 mA
Filtering time constant: 1 ms
24 VDC power output (X23)
Voltage: 24 VDC ±10%, short-circuit proof
Maximum output current: 250 mA (without any optional modules inserted)Relay outputs (X25, X26, X27)
General: Three programmable relay outputs
Switching capacity: 8 A at 24 VDC or 250 VAC; 0.4 A at 120 VDC
Minimum continuous current: 5 mA rms at 24 VDC
Maximum continuous current: 2 A rms
Isolation test voltage: 4 kVAC, 1 min
Slot 1 (X31)
General: For connection of I/O extension modules (such as RAIO and RDIO), pulse encoder interface (RTAC), or fieldbus adapters (such as RPBA and RMBA)Slot 2 (X32)
General: For connection of I/O extension modules (such as RAIO and RDIO) or pulse encoder interface (RTAC)
DDCS (X33)
General: For connection of RDCO-0x(C) DDCS Communication module
RDCU-02(C) Control Unit Hardware Manual
ACS800
10
24 VDC power input (X34)
Voltage: 24 VDC ±10%
Typical current consumption (without option modules): 250 mA
Maximum current consumption: 1200 mA (with option modules inserted)Pin designations: 1 = not used; 2 = +24 V; 3 = 0 V
Control panel connection (X39)
General: For connection of CDP-312R control panel
PPCS link (V57, V68)
General: Optical fibre connection to inverter (or IGBT supply) module
Optical component type: 10 MBd
Protocol: ABB PPCS (Power Plate Communication System)
Jumper J1
General: See Isolation and grounding below
Pitch: 2.54 mm
LEDs
“Power”: Green; denotes +5 V power OK
“Fault”: Red
Ambient conditions
Operating temperature: +0 … +60 °C (32…140 °F)
Storage temperature: -40 … +70 °C (-40 … +158 °F)
Applicable standards
Immunity: IEC 61800-3 (Limits: Industrial, Second environment); EN 50081-2 (Limits: Industrial)
Emission: EN 50081-2 (Limits: Industrial)
PELV requirements: The terminals of the RMIO board as well as on the optional modules attachable to the board fulfil the Protective Extra Low Voltage (PELV)
requirements stated in EN 50178 provided that the external circuits connected to the terminals also fulfil the requirements.
RDCU-02(C) Control Unit Hardware Manual
ACS800
11
Isolation and groundingX20
1
2
X21
1
2
3
4
5
6
7
8
9
10
11
12
X22
1
2
3
4
9
5
6
7
8
11
10
X23
1
2
X25
1
2
3
X26
1
2
3
X27
1
2
3
GroundRO3RO3RO3(Test voltage: 4 kV AC)RO2RO2RO2RO1RO1RO1+24 VGNDDI1DI2DI3DI4DGNDDI5DI6+24V+24VDIILDGNDorGrounds of input groups DI1…DI4 and DI5/DI6/DIIL are separate (isolation voltage 50 V).J1All digital inputs share a common ground. This is the default setting.Jumper J1 settings:VREFGNDAI1+AI1-AI2+AI2-AI3+AI3-AO1+AO1-AO2+AO2-Common mode voltage between channels ±15 VVREFGND(Test voltage: 500 V AC)
RDCU-02(C) Control Unit Hardware Manual
ACS800
12
Dimensions
RDCU-02(C) Control Unit Hardware Manual
ACS800
ACS800
ABB Oy
AC Drives
P.O. Box 184
FIN-00381 HELSINKI FINLAND
Telephone:+358 10 22 11 Fax:+358 10 22 22681 Internet:ABB Inc. Drives & Power Products 16250 West Glendale Drive New Berlin, WI 53151 USA Telephone:262 785-3200 800 243-4384 Fax:262 780-51353AFE 64636324 REV B / ENEFFECTIVE: 23.05.2005
正在阅读:
ACS800-RDCU-硬件手册-英文06-05
八年级政治期中考试试卷06-27
旅游学复习重点大纲11-01
我的小秘密作文1000字06-22
浅议如何在教学过程中贯穿德育教育-2019年精选文档03-11
2020年组织部长在全市新提拔副科级干部培训班上的讲话09-07
家是充满爱的海洋作文350字06-18
2010世辩表演赛辩词 - 生命的可悲可喜在于不可重来01-25
幼儿园下半年学前班数学期末试卷06-28
- 教学能力大赛决赛获奖-教学实施报告-(完整图文版)
- 互联网+数据中心行业分析报告
- 2017上海杨浦区高三一模数学试题及答案
- 招商部差旅接待管理制度(4-25)
- 学生游玩安全注意事项
- 学生信息管理系统(文档模板供参考)
- 叉车门架有限元分析及系统设计
- 2014帮助残疾人志愿者服务情况记录
- 叶绿体中色素的提取和分离实验
- 中国食物成分表2020年最新权威完整改进版
- 推动国土资源领域生态文明建设
- 给水管道冲洗和消毒记录
- 计算机软件专业自我评价
- 高中数学必修1-5知识点归纳
- 2018-2022年中国第五代移动通信技术(5G)产业深度分析及发展前景研究报告发展趋势(目录)
- 生产车间巡查制度
- 2018版中国光热发电行业深度研究报告目录
- (通用)2019年中考数学总复习 第一章 第四节 数的开方与二次根式课件
- 2017_2018学年高中语文第二单元第4课说数课件粤教版
- 上市新药Lumateperone(卢美哌隆)合成检索总结报告
- 英文
- 手册
- 硬件
- RDCU
- ACS
- 800
- 电视监控系统入门教材(6)
- 儿童家庭与社区教育
- 论辩诉交易与我国刑事诉讼法的修改——以效率及人权保障为视角
- 对荆门市饮用水市场调查报告
- 小学一年级学生数学学习习惯的培养
- 2015-2020年中国脲醛树脂胶市场运行格局及投资战略研究报告
- 北师大版四年级数学下册期末复习知识点梳理
- 《煤矿安全规程》知识竞赛复习题
- 四年级升五年级语文综合考试题 含答案
- 基于形状边缘方向直方图的图像检索算法研究
- 2010年国家社科基金民族问题研究立项(88项)
- 环评单位联系表(乙)
- 吉祥天宝分集剧情第14集(共40集)_吉祥天宝剧情介绍_吉祥天宝大结局_吉祥天宝演员表
- 2014年“中国石化-三井化学杯”第八届全国大学生化工设计竞赛设计任务书
- 晚会工作人员须知
- 矿山排土场安全现状评价报告(2)
- 课堂教学转型变革的策略研究(吴亚萍)
- 研究显示富钾食物有助预防心脑血管疾病
- 牛顿运动定律3经典临界问题
- 数据库设计关于图书馆管理系统的设计(有完整代码)