日本防爆等级分类

更新时间:2023-10-15 10:29:01 阅读量: 综合文库 文档下载

说明:文章内容仅供预览,部分内容可能不全。下载后的文档,内容与下面显示的完全一致。下载之前请确认下面内容是否您想要的,是否完整无缺。

先看d2G4定義: |' C- |: x( _% P, l D2G4是日本系統的安全規格 規格如下

Protection methods:

d = flameproof (same concept as in IEC 60079-1, 1990)1 n! O7 ?- g5 ~. r, @ e = increased safety (same concept as in IEC 60079-7, 1990)

i = intrinsic safety (same concept as in IEC 60079-11, 1991)- z2 B& a& Q4 }1 t o = oil immersion (same concept as in IEC 60079-6, 1968)

p = pressurization (same concept as in IEC 60079-2, 1983)& Q6 ^. |- L2 v/ a\

Note - The protection methods: 'm', 'q', and 'n', have not yet been adopted by the MHLW, and therefore are not available as a certification option through TIIS. Explosion grades (Gas groups in IEC):

1 = propane (same as IIA in IEC)0 N# W4 n3 ]( @; f) @9 h 2 = ethylene (same as IIB in IEC)/ I$ q: j. u, W 3a = hydrogen (same as IIB + H2 in IEC) 3b = carbon disulfide (IIB + CS2 in IEC) 3c = acetylene (IIB + C2H2 in IEC)

3n = all the gases in grade 3 (same as IIC in IEC) 8 [\

Ignition categories (Temperature codes in IEC):

G1 = 450°C (same as T1 in IEC) × 0.8 - 40°C = 320°C rise5 W; z+ C& T9 }3 j# a9 u G2 = 300°C (same as T2 in IEC) × 0.8 - 40°C = 200°C rise\ G3 = 200°C (same as T3 in IEC) × 0.8 - 40°C = 120°C rise. U0 L; @- }. O G4 = 135°C (same as T4 in IEC) × 0.8 - 40°C = 68°C rise G5 = 100°C (same as T5 in IEC) × 0.8 - 40°C = 40°C rise

G6 = 85°C (same as T6 in IEC) × 0.8 - 40°C = 28°C rise 5 B2 e: `9 O% m

以下則是國標定義

dⅡBT44 \\' ^; l9 P5 r+ L. j* _

d代表隔爆型,此项代表爆炸性气体环境电气设备的选型,即在爆炸性气体区域(0区、1区、2区)不同电气设备使用安全级别的划分。如旋转电机选型分为隔爆型(代号d)、正压型(p)、增安型(e)、无火花型(n);灯具类选型分为隔爆型(代号d)、增安型(e);信号、报警装置选型分为本质安全型(ia、ib)、隔爆型(代号d)、增安型(e)。 , Z* u4 O; X4 h( O

ⅡB代表气体或蒸气爆炸性混合物等级的划分,分为ⅡA、ⅡB、ⅡC三种,其中ⅡA最低(如通常的烷烃甲烷乙烷;芳香烃苯、甲苯),ⅡB类主要有丙炔、乙烯、环丙烷、1,2-环氧丙烷、焦炉煤气等;ⅡC最高(主要有氢、乙炔、二硫化碳、硝酸乙酯、水煤气等。这些等级的划分主要是依照最大试验安全间隙(MESG)或最小点燃电流(MICR)来区分的。

T4代表135<T≤200℃,它的定义是指能引燃某种介质的温度分组的划分。主要分为T1——450℃<T、T2——300<T≤450℃、T3——200<T≤300℃、 T4——135<T≤200℃、

T5——100<T≤135 、 T6——85<T≤100℃.

本文来源:https://www.bwwdw.com/article/o8if.html

Top