洲际酒店工程建设标准中英文对照版

1) STANDARDS SUMMARY

© InterContinental Hotels Group – Asia Pacific 2005 Revision All Rights Reserved

1

洲际酒店工程建设标准中英文对照版

1.1 1.2

SUMMARY

............................................................................................................................. 3

COMMON OMISSIONS AND PROBLEMS ......................................... 9

1.2.1 1.2.2 FIRE LIFE SAFETY .................................................................................. 9 MECHANICAL, ELECTRICAL AND PLUMBING .............. 11

© InterContinental Hotels Group – Asia Pacific 2005 Revision All Rights Reserved

2

洲际酒店工程建设标准中英文对照版

1.1

SUMMARY

Section

System General

RequirementsAll public areas fully air conditioned. Service areas ventilation except staff cafeteria, offices. HVAC in locations with average temp of o

13C >5hrs/yr.

AIR

CONDITIONING

Air changes & temperature

Guest rooms

13C/5

o

/

Public areas

As detailed in tables

Moderate climate: 4-pipe overhead fan coil, tropical: 2-

o

pipe. Temperature summer: 22C;

ooo

winter: 24C. Thermostat setting 23C +/- 3C.

4

o

o

2 o22C

24C

o

Swimming Pool – Indoors

23C +/- 3C

Fresh primary air/ exhaust: with thermal wheel heat recovery.

/ 90/85cbm/

Administration, Telephone Medium pressure multiple zone variable air

ooperator & Department head volume systems. 23oC. 23C

offices

Service areas

VAV with latent heat recovery. 28oC

o

28 C

Minimum fresh air/exhaust + inpidual fan coils

/ +

Staff cafeteria Computer room

Lift plant rooms

Laundry 100% fresh air/exhaust. 28C with spot cooling. o

100% / 28 C (

)

o

Kitchens Induction hood. 27C with spot cooling. o

27 C

oo

HVAC. 23C 23CIndependent self-contained unit. 23C.

o

23 C

Tropical locations: Self-contained unit, unless supplied by room exhaust

o

o

Equipment

洲际酒店工程建设标准中英文对照版

© InterContinental Hotels Group – Asia Pacific 2005 Revision All Rights Reserved

3

洲际酒店工程建设标准中英文对照版

ENGINEERING STANDARDS SECTION 1 – SUMMARY

Cooling Towers

Cross-flow/ induced draft-2speed fans. Not required

for air-cooled chillers. /

Boilers - Hot water

Cold climate <4C: 2 hot water units @

o

Warm climate >5C: 2@50%. of maximum demand. Diversity: 80%. 94% efficiency or heat pump.

o

<4 C 2 67%

2 units @ 100%. 3-pass water tubes boilers.

2 100%

o

Boilers – Steam

laundry.120

ppm cooling towers & hot water.

0 50 ppm

ppm

120 ppm

Dedicated water treatment systems for cooling towers, boilers, closed circuits heating & cooling

Water Treatment

洲际酒店工程建设标准中英文对照版

Kitchens Effluent

& Laundry

Grease traps for kitchen effluent. PH correction for laundry-as required.

PH

© InterContinental Hotels Group – Asia Pacific 2005 Revision All Rights Reserved

4

洲际酒店工程建设标准中英文对照版

ENGINEERING STANDARDS SECTION 1 – SUMMARY

Hot water

Duplex storage type with circulation pumps. Shell/tube heat exchangers. Where non-scale forming exterior plate/frame heat exchangers. General oo

supply: 60C. Dishwasher booster to 80C. Thermostatic anti-scald mixing valves in all public

o

areas to limit to 40C.

o

o

Irrigation

80 C

60 C

40 oC

Sub-surface automatic piping system

Storm drainage

Materials

Separate system discharging into sewer, combination sewer as per local situation.

Domestic water: copper or Pool, fountains, irrigation: PVC. Stand-pipe, sprinklers, heating, cooling: BS. Sewer: Cast iron or PVC (Insulated).

PVC

BS

PVC

Sewage Treatment Plant

As required and/or feasible for recycling.

/

Tub: 3.5 mm steel, white. Showerhead:

mixer. Tap:

6 ltrs/min. Toilet: 6/3 ltrs dual flush. 3.5 mm 13 / Requirements

Bathrooms

Section

System Supply

ELECTRICAL

Gas & Fuel

Swimming Pool

HV loop to air-cooled transformers rated at 2*100% or

3*50% capacity. High or low voltage 6/3

per local code & best tariff. Power factor correction. As per local conditions-most feasible supply.

2*100% –

Emergency Power

o

Dedicated water treatment. Indoor pool heated to 28C. 3*50%

o 28 C

Distribution

Emergency generator for all life safety systems, lifts, partial lighting, coldrooms, domestic & sump pumps & specific other equipment. Fuel, enough

for 48 hours. UPS for all computer equipment.

Guest Rooms

洲际酒店工程建设标准中英文对照版

© InterContinental Hotels Group – Asia Pacific 2005 Revision All Rights Reserved

5

洲际酒店工程建设标准中英文对照版

ENGINEERING STANDARDS SECTION 1 – SUMMARY

Lighting

As per interior designer, IC room & other standards.

Dimming for all public areas except corridors, rooms.

Audio-visual

MATV & Sound systems for all rooms, specific public areas. Pocket paging system.

Communication

system.

,

& Data See separate standards

Systems

ELEVATORS

Guest Elevators

Adequate number to answer all calls within 30 seconds for 50%, 45 sec. for 95%, 60 sec. for 100% of waiting persons. 30 50%

45 95% 1

Service Elevators

Minimum of two (2) units for hotels 400 rooms, but minimum of 50% of guest elevators. 400

2

Banquet

50%

Larger elevator to accommodate all guests within 30

minutes and transport exhibition goods (car etc).

30

Firemen's lift

As required by local code.

Escalators

As required by layout.

洲际酒店工程建设标准中英文对照版

© InterContinental Hotels Group – Asia Pacific 2005 Revision All Rights Reserved

6

LIFE SAFETY

Suppression

Fire Detection & Alarm

Fully sprinklered building, concealed quick response

type.

2.5" fire hoses in high rise; low rise at discretion of IHG

2.5"

Fire extinguishers throughout

Kitchen hood: Wet chemical ext. system

Computer room: Pre-action dry sprinkler

Section

System RequirementsInterfaces with paging systems, BMS, smoke control systems, elevator recall, other ext. sub-systems, door

洲际酒店工程建设标准中英文对照版

ENGINEERING STANDARDS SECTION 1 – SUMMARY

BMS

Guest rooms: Addressable smoke detector with integral acoustic alarm

Central Control Room

All high-rise

Emergency Power

Generator for all life safety systems, lifts, telephone

system, lighting: 15% public area, 20% service areas,

100% stairs, exit signs, GM's apartment, doctor's office, engineering office, generator & switchgear rooms. Vestibule in each guestroom.

15%

20%

100%

Non-life safety: sump pumps, domestic water refrigeration, computer systems

Emergency Exit Signs

Battery back-up

Atrium exhaust

Smoke Control

Stair pressurization in high-rise.

Guest rooms corridor smoke exhaust via ventilation system- built to higher standard.

Smoke Doors Can be omitted in fully sprinklered building-unless req. by local code.

Fire Dampers

All fire-rated walls. 2 hours and over. 2

ENERGY

MANAGEMENT

GENERAL UTILITY CONSUMPTION

Annual consumption shall not exceed per square meter net area the following in climate zones: Moderate: 145, Mediterranean: 155, Tropical: 200 KWh/sqm/year.

Electricity

洲际酒店工程建设标准中英文对照版

145

155

/

Peak demand: Moderate: 2.5 KW/room, Mediterranean: 2.7 KW, Tropical: 3.5 KW.

2.5 /

200 /

2.7 /

3.5 /

Energy (net calorific value

& net energy available at boiler discharge)

Annual consumption shall not exceed per square meter net area the following in climate zones: Moderate: 180, Mediterranean: 140, Tropical: 80 KWh/sqm/year.

&

180 /

140

80 /

© InterContinental Hotels Group – Asia Pacific 2005 Revision All Rights Reserved

7

洲际酒店工程建设标准中英文对照版

ENGINEERING STANDARDS SECTION 1 – SUMMARY

District heating peak demand: Moderate climate: KW/room. 6 /

6

Water

Moderate: 560 Tropical: 900.

ltrs/guest, 560 900/

/

Mediterranean:

600, 600/

Air Conditioning

K-factors for wall construction: 0.35; windows: 1.3.

K 0.35 1.3

boilers, heating etc.

Section

System Requirements

Centr. & screw chillers shall have an efficiency of

<0.55 KWh/ton, boilers: 91%.

& <0.55

KWh/ton 91%

Air conditioning systems shall be variable air volume

Thermal wheel heat recovery for all systems >10,000 cbm/hr. Indoor pool with latent heat recovery to heat pool water.

>10,000 cbm/hr

Secondary heating & cooling water systems shall have variable speed drives.

District heating: air conditioning systems shall be designed for maximum temp. spread, e.g.

o

70/50C, fan coils 60/40oC. Hot water heating shall have pre-heating via recovery from common return.

70/50C

o

60/40C

o

Building Automation system with detailed energy control functions.

PLUMBING

Induced draft cooling towers with variable speed fans, controlled from chiller for max. efficiency.

洲际酒店工程建设标准中英文对照版

© InterContinental Hotels Group – Asia Pacific 2005 Revision All Rights Reserved

8

洲际酒店工程建设标准中英文对照版

ENGINEERING STANDARDS SECTION 1 – SUMMARY

5

All toilets 6/3 ltrs dual flush.

6/3

All sink faucets in rooms, public areas, staff lockers 6

ltrs/min.

6 /

All showerheads in staff lockers 9 guest

rooms 13

ltrs/min.

9 / 13 /

Sub-metering of all major departments

Automatic sub-surface irrigation with timers, humidity

sensors.

Water treatment to all open systems to prevent scale

shall be recovered for further treatment to reduce losses by

90%.

90%

Laundry: Washing machines w. recovery or

tunnel washers.

洲际酒店工程建设标准中英文对照版

1.2 COMMON OMISSIONS AND PROBLEMS

1.2.1

FIRE LIFE SAFETY

© InterContinental Hotels Group – Asia Pacific 2005 Revision All Rights Reserved

9

Section

System ELECTRICAL

RequirementsCheapest electricity tariff. Power factor correction.

Peak demand control via BMS, where applicable

BMS

Lighting: Efficient compact fluorescent in all public areas, unless decorative effect restricts use.

All corridor lighting to shut off via timers or motion detectors. Exception: Emergency Exit Signs.

Motion detectors for public toilets, luggage room, staff lockers, cafeteria, banquet rooms

洲际酒店工程建设标准中英文对照版

ENGINEERING STANDARDS SECTION 1 – SUMMARY

1. Sprinklers are to be provided in all plantrooms.

2.

All fire rated doors must be certified as to their rating.

3. Fire dampers must be installed where air ducts penetrate 2-hr fire rated walls and floor and

must be fitted at the wall floor penetration.

2

4.

Dead end corridors must be minimum 8m in length in new constructions.

8

5.

Egress corridors must be minimum 1120mm in width.

11200

6. Exit doors must be minimum 815mm wide.

815

7. Fire Stairs must exit at ground level to an area outside the building.

8.

Smoke detectors are required in all areas, including store rooms, pantries and at the top of all

fire stairs.

9.

Smoke detectors to be spaced at 9-10m between adjacent detectors or 1 detector per 85m².

9-10 8.5

10.

25 detectors maximum per zone, all must be addressable.

25

11.

All fire pumps and jockey pumps must have status displayed at fire control room for running, fault and auto mode.

12. Guestroom detectors must have a buzzer or audible base.

13.

Common problems with detector locations include: too low from ceiling, too close to supply air grill, placed in nuisance areas.

14.

All wiring to smoke detectors, heat detectors, speakers must be class A. A

洲际酒店工程建设标准中英文对照版

15.

Evacuation speakers are required in all areas, including public toilets, staff areas, back of the house offices, boilers rooms, chiller rooms, switchgear rooms, Genset rooms, stores and elevators.

16.

Horn type speakers with strobes to be used where ambient noise level is high.

© InterContinental Hotels Group – Asia Pacific 2005 Revision All Rights Reserved

10

洲际酒店工程建设标准中英文对照版

ENGINEERING STANDARDS SECTION 1 – SUMMARY

17. Evacuation speakers to have fire proof back box.

18. Guestroom sidewall sprinklers to be extended coverage type, quick response.

19.

Sprinklers are required in bathrooms exceeding 5sqm.

5

Test drain to be provided after each flow switch in sprinkler pipework at convenient location.

20.

21.

Combustible ceiling voids over 800mm to have upper layer of sprinklers.

800

22. Piping to be hydrostatically tested at not less than 13.8 bars or 3.8 bar in addition to

highest

system pressure when system working pressure is 10 bars. (Not to exceed 12 bars)

13.8

10

12

3.8

23. Fire water reserve should be sufficient for one hour full operation.

24. Side wall sprinkler is often mounted too low from ceiling (150-300mm maximum).

150 – 300

25. Jockey pump oversized resulting in main sprinkler pump not operating when a

sprinkler is

activated.

26. Hose reels are to be located externally of the fire escape stairs.

27. Adjustable fog nozzles are required on hose reels.

28. Computer room to be protected with wet sprinklers.

29.

Sprinkler isolation construction valves left in system. All valves must be removed or have tamper proof alarm fitted.

30.

Dry pendant sprinkler heads are required in freezers and coolrooms.