Configuring the OMRON FINS Gateway I/O Server Using the Serial Unit
Configuring the OMRON FINS Software
1. Start the FinsGateway Service Control Manager. Verify the CPU Unit and SerialUnit are running. You can also select Property then Automatic startup for both the CPU Unit and SerialUnit.
Figure 1. Verifying Services
2. Open FinsGateway Network Navigator. Highlight the COM1 Serial Unit and click
the Property button.
Figure 2. FinsGateway Network Navigator Window
3. Next, select the Network tab. The Local Node number and the Communication
Unit number should be automatically selected.
Figure 3. Network Tab
4. Select the Communication Unit tab. Configure the proper Com Port parameters.
Figure 4. Communication Unit Tab
5. Select the Nodes tab and click the Add button. Enter the proper parameters
for the PLC and click OK.
Figure 5. Adding Seiral Node Under the Nodes Tab
6. Select the Lines tab. Use the check boxes to select the port that will be
active. When complete, click the Apply button, then the Close button.
Figure 6. Selecting Active Port
7. Next, start the FINS Network Tester. In the Peer field, enter the Node,
Network, and Unit of the PLC (refer to Figures 3 and 5). In the Send Message field, enter 0501. Click the Start button. If communications is successful, then send and receive messages will be displayed as shown in Figure 7. If communications cannot be established, then a Timeout message or an error message will appear in the Comment field.
If communications to the PLC is not successful, re-check the FINS Software configuration and cabling.
Figure 7. Testing Communications
Configuring a Topic for the Wonderware OMRON FINS Gateway I/O Server
Start the OMRON FINS Gateway I/O Server. From the Server menu bar, click on Configure and then select Topic Definition. The Topic Definition dialog box should appear. Click the New button and define your Topic as shown in Figure 8.
In this example, Network is 0 (see Figure 3), Node is 1 and Unit is 1 (see Figure 5).
Figure 8. Configuring a Topic
Testing Communications with WWClient
1. Open WWClient. Click Connect from the menu bar if using WWClient V7.0, or
click Connections/Create if using WWClient V7, 0, 0, 1 or greater.
2. Enter the following data to connect to the OMRON FINS Gateway I/O server:
o Application: Enter finsgtwy
o Topic Name: Enter the topic name created in Figure 8.
In this example, we used c200hs. o Connection Type: Select DDE or IOT
Figure 9. Connecting to the Server
3. When complete, click Connect then Done.
4. Next, from the WWClient menu bar click on Item . An Item dialog box should
appear showing a highlighted connection as shown in Figure 10. In the Item field, enter a valid PLC address.
5. Select the data type in the drop-down list box, in this case an Interger,
and click the AdviseEx button.
Figure 10. Item Dialog Box
6. In the WWClient window, you should now see a value to the right of the item
name. Notice the hex value, 0x00c0, at the end of the item name line. This value indicates good data quality. Any other value indicates bad data quality. The WWLogger will display more detailed information concerning a communications failure.
Figure 11. WWCient Window
正在阅读:
OMRON - FINS GatewayIO Server设置方法04-09
电厂值长调度证取证试题 0207-10
液压习题答案10-10
秋季幼儿园教师个人工作计划01-13
阿尔卑斯棒棒糖广告策划方案03-11
建筑企业投资PPP项目的风险及对策07-26
全面建设小康社会统计监测工作实施办法12-02
双歧乳酸菌饮料项目可行性研究报告(发改立项备案+2014年最新案例范文)详细编制方案03-14
学游泳基本知识-杠杠的07-19
世界现代设计史01-24
- 多层物业服务方案
- (审判实务)习惯法与少数民族地区民间纠纷解决问题(孙 潋)
- 人教版新课标六年级下册语文全册教案
- 词语打卡
- photoshop实习报告
- 钢结构设计原理综合测试2
- 2014年期末练习题
- 高中数学中的逆向思维解题方法探讨
- 名师原创 全国通用2014-2015学年高二寒假作业 政治(一)Word版
- 北航《建筑结构检测鉴定与加固》在线作业三
- XX县卫生监督所工程建设项目可行性研究报告
- 小学四年级观察作文经典评语
- 浅谈110KV变电站电气一次设计-程泉焱(1)
- 安全员考试题库
- 国家电网公司变电运维管理规定(试行)
- 义务教育课程标准稿征求意见提纲
- 教学秘书面试技巧
- 钢结构工程施工组织设计
- 水利工程概论论文
- 09届九年级数学第四次模拟试卷
- GatewayIO
- 设置
- 方法
- Server
- OMRON
- FINS